The Effect of Compressor Speed Variation and Vapor Injection on the Performance of Modified Refrigeration System
(*) Corresponding author
DOI: https://doi.org/10.15866/ireme.v12i3.14192
Abstract
This work presents an experimental and numerical investigation of vapor compression refrigeration system performance with variable speed compressor and vapor injection. A test rig of 5 ton capacity split air conditioner equipped, with frequency inverter to control the speed of scroll type compressor, and a secondary capillary tube to expand the refrigerant in the vapor injection circuit are used to conduct the experimental work. Three different vapor injection mass ratios (2, 3, and 4%) are investigated with variable compression speed for frequency range from 35 to 60 Hz. TRNSYS-16 is the software is used to simulate a single zone building conditioned with the modified split air conditioner. The results showed that, the reduction of the compressor speed to the frequency of 35Hz leads to an improvement of the COP by 36% and reduces the power consumption by 18%, compared to the conventional refrigeration system. The usage of the vapour injection with variable speed compressor has improved the COP of the modified system by 47% at 35 Hz and 2% vapour injection ratio. The average improvement in cycle capacity at different compressor speeds is about 24.6%, 28.77% and 34.28% respectively for the vapor injection ratios of 2%, 3& and 4%. It was observed that the reduction of compression speed can extend the compressor lifetime by reducing the ON/OFF cycle of the system at a speed of 35Hz and 2% vapor injection by 17.3%, compared to the conventional system. While at a speed of 60Hz, the ON/OFF cycle has increased by 9.3 and 12% for 2% and 4% injection ratios, respectively. The comparison between the numerical and experimental results of the modified system with vapor injection ratio 2% and 35 Hz compressor speed has displayed an increase in the numerical results around 2.57% for COP, 5.8% for cooling capacity and 5.68% for compressor power consumption.
Copyright © 2018 Praise Worthy Prize - All rights reserved.
Keywords
Full Text:
PDFReferences
Koury, R. N. N., Machado, L., & Ismail, K. A. R., Numerical simulation of a variable speed refrigeration system. International Journal of Refrigeration, Vol. 24(2), pp. 192-200, 2001.
http://dx.doi.org/10.1016/s0140-7007(00)00014-1
Binneberg, P., Kraus, E., and Quack, H., Reduction in Power Consumption of Household Refrigerators by Using V variable Speed Compressors. International Refrigeration and Air Conditioning Conference. Paper 615, 2002.
Shao, S., Shi, W., Li, X., & Chen, H., Performance representation of variable-speed compressor for inverter air conditioners based on experimental data. International journal of refrigeration, Vol. 27(8), pp. 805-815, 2004.
http://dx.doi.org/10.1016/j.ijrefrig.2004.02.008
Yang D. S., Lee G., Kim M. S., Hwang Y. J., Chung B. Y., A study on the capacity control of a variable speed vapor compression system using superheat information at compressor discharge, 10th Int. Refrig. Conf. at Purdue, West Lafayette-IN, USA, Paper R-164, 2004.
Li, H., Jeong, S. K., Yoon, J. I., & You, S. S., An empirical model for independent control of variable speed refrigeration system. Applied Thermal Engineering, Vol. 28(14), pp. 1918-1924, 2008.
http://dx.doi.org/10.1016/j.applthermaleng.2007.12.008
Ekren, O., Sahin, S., & Isler, Y., Comparison of different controllers for variable speed compressor and electronic expansion valve. International Journal of Refrigeration, Vol. 33(6), pp. 1161-1168, 2010.
http://dx.doi.org/10.1016/j.ijrefrig.2010.05.005
Henery N., Afiq A. Dahlan, Affandi M. Nasib, Azhar A. Aziz,, Performance of a Variable Speed of the Split Unit Air Conditioning System using Fuzzy Logic Controller. Proceedings of the International Multi Conference of Engineers and Computer Scientists , Hong Kong , Vol. I, IMECS, March, pp. 18-20, 2015.
http://dx.doi.org/10.4028/www.scientific.net/amm.819.212
Lee, C. K., Dynamic performance of ground-source heat pumps fitted with frequency inverters for part-load control. Applied Energy, Vol. 87(11), pp. 3507-3513, 2010.
http://dx.doi.org/10.1016/j.apenergy.2010.04.029
Madani, H., Claesson, J., and Lundqvist, P., Capacity control in ground source heat pump systems part II: Comparative analysis between on/off controlled and variable capacity systems. International journal of refrigeration, Vol. 34(8), pp. 1934-1942, 2011.
http://dx.doi.org/10.1016/j.ijrefrig.2011.05.012
Xudong Wang, Yunho Hwang, and Reinhard Radermacher, Performance Investigation of Refrigerant Vapor-Injection Technique for Residential Heat Pump Systems. International Refrigeration and Air Conditioning Conference. Paper 901, 2008.
Awan, U. K., Experimental analysis of variable capacity heat pump system equipped with vapour injection and permanent magnet motor, Masters of Science Thesis, Stockholm, Sweden, 2012.
Siddharth J., Gaurav J. and Bullard, C. W., Vapor injection in scroll compressors, International Compressor Engineering Conference, Purdue University, July 12-15, 2004.
Colmek, Sophie, and Laurent Goderneaux, Gas Vapor Injection on Refrigerant Cycle Using Piston Technology, International Refrigeration and Air Conditioning Conference. Paper 1220, 2012.
Safa, A. A., Fung, A. S., and Kumar, R. C, Performance of two-stage variable capacity air source heat pump: Field performance results and TRNSYS simulation. Energy and Buildings, Vol. 94, pp.80-90, 2015.
http://dx.doi.org/10.1016/j.enbuild.2015.02.041
Winandy, E. L., and Lebrun, J., Scroll compressors using gas and liquid injection: experimental analysis and modelling. International Journal of Refrigeration, Vol. 25(8), pp. 1143-1156, 2002.
http://dx.doi.org/10.1016/s0140-7007(02)00003-8
Wang, B., Li, Xianting, Shi, Wenxin, and Yan, Qisen, Effects of Refrigerant Injection on the Scroll compressor, International Compressor Engineering Conference. Paper 1770, 2006.
Bell, I., Groll, E., Braun, J., and Horton, W. T., Simulation of a coldclimate heat pump furnished with a scroll compressor with multipleinjection lines, International Conference on Compressors and their Systems, 2013.
Bach, C. K., Groll, E. A., Braun, J. E., Horton, W. T., and Vetsch, B., Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps, Paper AM-4249223, in 11th IEA Heat Pump Conference, pp. 12-16, 2014.
Yan, G., Jia, Q., and Bai, T., Experimental investigation on vapor injection heat pump with a newly designed twin rotary variable speed compressor for cold regions, International Journal of Refrigeration, Vol. 62, pp. 232-241, 2016.
http://dx.doi.org/10.1016/j.ijrefrig.2015.10.024
Cho, I. Y., Seo, H., Kim, D., & Kim, Y., Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes, Energy, 112, 179-187, (2016).
http://dx.doi.org/10.1016/j.energy.2016.06.069
Oquendo, F. M. T., Peris, E. N., Macia, J. G., and Corberán, J. M., Performance of a scroll compressor with vapor-injection and two-stage reciprocating compressor operating under extreme conditions. International Journal of Refrigeration, Vol. 63, pp. 144-156, 2016.
http://dx.doi.org/10.1016/j.ijrefrig.2015.10.035
Bertrand D., Samuel G., Vincent L., Stéphane B. ,Experimental investigation and dynamic modelling of an air-to-water residential heat pump with vapor injection and variable speed scroll compressor, 12th Heat pump conference, Rotterdam, 2017.
Burkholder, F., TRNSYS Modeling of a Hybrid Lighting System: Energy Savings and Colorimetric Analysis, Mechanical Engineering Department, University of Wisconsin-Madison, Master of Science Thesis, 2004.
Paul McKenna and Donal P. Finn, A TRNSYS model of a building HVAC system with GSHP and PCM thermal energy-component modelling and validation, Proceedings of BS201313th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28, 2013.
Khosravi Bakhtiari, H., Developing a dynamic model of ground-source heat pump system to evaluate different components sizes, School of Industrial Technology and Management Royal Institute of Technology, Stockholm, Sweden, Master of Science Thesis, 2014.