Open Access Open Access  Restricted Access Subscription or Fee Access

Single Phase Fault Location in Distribution Networks Based on Charge Transients


(*) Corresponding author


Authors' affiliations


DOI: https://doi.org/10.15866/iree.v10i1.5033

Abstract


In this paper the one possibility of single phase fault location in unearthed MV distribution network is presented. This method is based on transients which appear in the case of charge redistribution in the instance of fault occurrence. The issues of fault location in distribution networks was emphasized through influence of inhomogeneity, distributed loads, considerable fault resistance and numerous branches on distribution feeders. On the extracted transients of currents and voltages of faulty phase, method based on solving differential equations is applied. The low frequency charge transients, with minimum sample frequency of several kHz is used. This method was examined by computer simulations on the modeled network as well as on the real network and fault. In the case of real fault, it was used data registered by power quality analyzer.
Copyright © 2015 Praise Worthy Prize - All rights reserved.

Keywords


Distribution Medium Voltage (MV) Network; Fault Location; Charge Transients

Full Text:

PDF


References


F. Božuta, „Automatski zaštitni uređaji u elektroenergetskim postrojenjima“ (eng. “Automatic protection devices in power plants“), Svjetlost, Sarajevo, 1989.

Technical documentation and statistics of faults in the MV network, taken from the Electric Power Industry of Bosnia and Herzegovina (JP EP BiH) and ED Tuzla, from 2005 to 2010

J.A.Jardini et.al., „Daily Load Profiles for Residential, Commercial and Industrial Low Voltage Consumers“, IEEE Trans on Power Delivery, January 2000.
http://dx.doi.org/10.1109/61.847276

R. Das, M.S. Sachdev, T.S. Sidhu, „A Fault Locator for Radial Subtransmission and Distribution Lines“ IEEE Power Engineering Society Summer Meeting, Seattle, Washington, USA, July 2000.
http://dx.doi.org/10.1109/pess.2000.867627

Mokhlis, H., Li, H.Y., Khalid, A.R., The application of voltage sags pattern to locate a faulted section in distribution network, (2010) International Review of Electrical Engineering (IREE), 5 (1), pp. 173-179.

Mokhlis, H., Bakar, A.H.A., Talib, D.N.A., Mohamad, H., The improvement of voltage sags pattern approach to locate a fault in distribution network, (2010) International Review of Electrical Engineering (IREE), 5 (3), pp. 1159-1164.

M. Lehtonen at. all, „Fault Management in Electrical Distribution Systems“, Final report of the CIRED working group WGO3 Fault management, Espoo, December 1998.

Seppo Hanninen, “Single phase earth faults in high impedance grounded networks, Characteristics, indication and location”, Doctoral Dissertation, Helsinki University of Technology, Espoo, Finland

Š. Gruhonjić Ferhatbegović „Single phase fault location in distribution network based on traveling waves“, Doctoral Dissertation, Faculty of Electrical Engineering and Computing, May 2012. Zagreb, Croatia

Ferhatbegovic, S.G., Marasic, A., Pavic, I., Single phase fault distance estimation in medium voltage distribution network based on traveling waves, (2012) International Review of Electrical Engineering (IREE), 7 (1), pp. 3532-3541.

Y.G. Paithankar, „Transmission Network Protection“, Theory and Practice, M.D. New York 1997.

A. G. Phadke, J.S. Thorp, „Computer Relaying for Power Systems “, John Wiley and sons, New York 1988.

Matlab – SimPowerSystems, User’s Guide, Hydro – Quebec, Mathworks, September 2009.

Documentation of JP EP BiH: "Pilot projects for monitoring power quality," Sarajevo 2011.